FUSE / MCB Test Set ....

FUSE/MCB TEST SET Designed & Developed by PRESTIGE ELECTRONICS is ideally suited to determine current versus time characteristics of various types of fuses, circuit breaker MCB etc. Different models are available to suit different ratings & applications.

System consists of precision regulated, Very low ripple, variable DC constant current source, multirange time interval meter which indicates the time taken for fuse to blow.

Specification :
Output Current: 0-25, 0-50, 0-75, 0-100 or to 300A adjustable by coarse &
                        fine controls.
Time Interval Meter : 6 Digit 12.5mm Red LED.
a) Range: 9999.99 or 99999.9 Sec
b) Resolution: 0.01 Sec. & 0.1 Sec. respectively.
c) Accuracy: 0.05% ± 2 Digits.
Open Circuit Voltage : 4 to 5 V.DC
Supply : 230V.AC ± 15%,  50Hz, or 415V.AC 3 PHASE
Metering : Digital Current Meter
Multirange Time Interval Meter
Digital Millivolt Meter 0.2000mV.DC
Digital Temperature Indicator (Optional)
Operation :
System is very easy to operate as follows.
Switch on the instrument.
Press the reset push-button to reset the Time interval meter & keep current zero.
Set desired value of current to be passed by means of coarse,fine controls & set measure switch.
Select desired Time interval meter range.
Connect FUSE/MCB under test.
Press START pushbutton.
Instantaneously set value of current will pass through the FUSE/MCB
& Time interval meter starts counting time.
The instant at fuse blows, Time Interval meter stop counting & audio buzzer indicating the fuse blown condition.
Note the time for the fuse to blow.
Press RESET pushbutton.
Connect new fuse & repeat the same procedure. If required adjust the set value
of current.
Outstanding Advantages Of FUSE/MCB Test Set
Very easy to set test current down to 0.1% resolution. ( Third & Fourth digit ) simply by means of SET / MEASURE switch, coarse & fine potentiomatric controls only. NO EXTERNALARRAYS OF RHEOSTAT OR LOAD IS REQUIRED, INSTRUMENT IS COMPLETE BY ITSELF.
Either set current or test current can be displayed at any instant by SET / MEASURE switch.
Value of test current remains constant irrespective of mains supply variation or load  variation.

Test current is regulated DC with very very low ripple. Therefore R.M.S. average & peak value of current is same hence metering problems due to waveform distortions are not encountered.

Response is very fast hence measurement of time down to fractions of second possible.

Operation at production line is very simple because operator has to simply press START button, on tripping audio buzzer sounds there by alerting the operator.
Equipment can also be used for :
Since the value of test current is constant & separate Millivolt meter is provided, it can be used to monitor Millivolt drop of FUSE / MCB, contact etc.
Digital Temperature Indicator with suitable thermocouple can be provided to monitor temperature raise.